1:5:10:112 EcoTip: Doors are deliberately undercut to provide a path for airflow created by central heat and air systems. If the room has both a supply and return register – and is balanced as described in EcoTip:111 The undercut isn’t necessary. If you only have supplies registers in a room – but no returns – then the air must have a path to follow back to the central system to provide proper ventilation. This is provided by the space under the door. The door undercut may not be enough in which case you need to undercut it more or provide an RAP.

 

Tamarak Technologies Return Air Pathway

***********************************

 Additional Information

Suggested Review – :111

The amount of gap under the door is important to allow good air exchange and prevent pressure differences from developing in the house. Many builders cut a standard half-inch to one inch gap without understanding that size does matter. If carpet is installed, it may close the gap as well.

A 30 inch door with a half-inch gap can handle up to 25 cubic feet per minute (cfm) of air coming from the supply register in that room when the door is closed. To handle 75 cfm it would be necessary to have a 1.5 inch gap. If the gap isn’t big enough then back-drafting can occur (more on this in tomorrow’s tip).

Tamarack Technologies has informtion about the necessary door way undercuts or as an alternative you can use their Return Air Pathways (RAPs) instead of needing to undercut a huge gap under the door.